REACTOR SCRAM ON TOTAL LOSS OF OFF-SITE AC POWER (CLASS IV). SRUOR-1-90-9.

On 24.11-90, due to sudden loss of generation in the grid, the system frequency crashed down and caused unit-1 generator lock out on under frequency. GEB/MSEB feeders connected to Tarapur-1 tripped due to fault/disturbance in grid. Station lost off-site power. Unit-1 reactor scrammed due to de-energising the safety system relays. Normal recovery actions were taken.
BASIS FOR RATING: Degradation in defence-in-depth. Table A-1R, 0/1. All safety systems/functions were available. Reactor trip proceeded normally. Rating -0.
DIFFICULTIES IN RATING: None.

Location: TARAPUR-1
Event date: Sat, 24-11-1990
Nuclear event report