LOSS OF INTERNAL POWER DUE TO THE TRIP OF THE MAIN TRANSFORMER (T-1)

Loss of internal power due to the trip of transfromer T1 because of the activation of relay 286/GT, when the down side touch ground producing scram and isolation, with the plant being in condition 5, the GD-II started and delivered the loads in a sequential form, with the back up transformer (T-5). Bus - 1A1 was fed. Recovering scram and isolation. The event lasted 13 seconds.
Initiator event: None; frequency: possible; availability: adequate. Original classification "1" (from Table 1 column 2C from the INES users manual).

Location: LAGUNA VERDE-1
Event date: Fri, 18-09-1992