INES-event
INES 2

TG 2 TRIP DUE TO DEENERGIZATION OF 6 & 0.4 KV BUSES AND FAILURE OF TG STANDBY OIL PUMP TO START

While connecting DG-5 to essential bus during routine test the bus section was deenergized. This caused the stop of TG2 lub-oil system pump fed by this bus. Due to defect in standby feature activation system the standby oil pump failed to start. A signal of oil tank level and oil pump discharge pressure decrease was formed and TG-2 was tripped by protection system. Reactor power was reduced to 50% nom. by TG trip protection. The cause of bus failure was wrong connection of DG5 power cable to the bus after maintenance.
BASIS FOR RATING: Initiator - essential bus deenergization. Event expected, real. Safety function availability within safe operation limits and conditions, which corresponds to level 1/2 (B-1R). The event showed personnel errors, that demonstrate poor "safety culture", therefore the maximum level has been chosen.
DIFFICULTIES IN RATING:

Location: IGNALINA-1
Event date: Thu, 04-10-1990